UPS of type of ZT-HR series frame Power limits Power limits: 6kVA Working way
Power limits: 6kVA
Machine kind | ZT-HR1101(S)L | ZT-HR1102(S)L | ZT-HR1103(S)L | ZT-HR1106(S)L | ZT-HR1110(S)L | ||||||
Phasic | Single-phase ground connection | ||||||||||
Capacity | 1000VA / 800 W | 2000VA / 1600 W | 3000VA / 2400 W | 6000VA / 4800 W | 10000VA / 8000 W | ||||||
Input | |||||||||||
Rated voltage | 100/110/115/120/127VAC? Or 200/208/220/230/240VAC | 208/220/230/240VAC | |||||||||
Voltage limits | 55-145VAC or 110-300 VAC at 50% laden
85-140VAC or 160-280 VAC at 100% load | 110-300VAC ± 3% at 50% laden
176-300VAC ± 3% at 100% load | |||||||||
Frequency limits | 40Hz? ~ 70 Hz | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz | |||||||||
Power factor | ≧ 0.99 @ 100% is laden | ||||||||||
Output | |||||||||||
Rated voltage | 100/110/115/120/127VAC? Or 200/208/220/230/240VAC | 208/220/230/240VAC | |||||||||
Voltage limits? (Batteries mode) ) | ± 1% | ± 1% | |||||||||
Frequency limits? (Synchronous and corrective limits) | 47~ 53 Hz or 57 ~ 63 Hz | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz | |||||||||
Frequency limits (batteries mode) | 500.25 Hz of Hz ± or 0.3 Hz of 60Hz ± | 500.1 Hz of Hz ± or 0.1 Hz of ± of 60 Hz | |||||||||
Voltaic wave Zuo is compared | 3: 1 | ||||||||||
Harmonic is lack fidelity | Linear of ≦ 3 % THD (is laden) 5 % THD (of; ≦ is nonlinear laden) | Linear of ≦ 3 % THD (is laden) 5 % THD (of; ≦ is nonlinear laden) | |||||||||
Changeover time | Town report mode turns batteries mode | Without | |||||||||
Inversion comes bypass | 4 millisecond? (Below standard condition) | 0 millisecond | |||||||||
Undee (batteries mode) | Sterling bowstring wave | ||||||||||
Efficiency | |||||||||||
Town report mode | 88% | 89% | 90% | 92% | 93% | ||||||
Batteries mode | 83% | 87% | 88% | 90% | 91% | ||||||
Batteries | |||||||||||
Standard machine | Cell type | 12V / 9 AH | 12V / 9 AH | 12V / 9 AH | 12V / 9 AH | ||||||
Amount | 2 | 4 | 6 | 16 | 20 | 16 | 20 | ||||
The standard charges time | 4 hours are filled to 90% | 9 hours are filled to 90% | |||||||||
The biggest charging current | 1.0A (the biggest) | Set beforehand: 1.0 A, the biggest. : 2.0A | |||||||||
Charge voltage | 27.4VDC ± 1% | 54.7VDC ± 1% | 82.1VDC ± 1% | 218.4VDC ± 1% | 273VDC ± 1% | 218.4VDC ± 1% | 273VDC ± 1% | ||||
Grow effect machine | Cell type | Match according to actual application many batteries box | |||||||||
Amount | 2 | 3 | 4 | 6 | 6 | 8 | 16 ~ 20 (but Zha is whole) | ||||
The biggest charging current | 1.0A/2.0A/4.0A/6.0 A | 1A/2A/4A/6A (can be adjusted, 6A applies to 16 batteries only) | |||||||||
Charge voltage | 27.4VDC ± 1% | 41.0VDC ± 1% | 54.7VDC ± 1% | 82.1VDC ± 1% | 82.1VDC ± 1% | 109.4VDC ± 1% | 218.4VDC ± 1% (be based on 16) | ||||
Indication specification | |||||||||||
LCD Or LED shows | Laden size, ? Batteries capacity, town report mode, batteries mode, ? Bypass mode, breakdown directive | ||||||||||
Warn sound | |||||||||||
Batteries mode | Every 4 seconds ring | ||||||||||
Batteries n is low | Every 1 second rings | ||||||||||
Overload | Every 1 second rings | ||||||||||
Breakdown | Resound continuously | ||||||||||
Physical function | |||||||||||
StandardMachine | Dimension, deep X wide X is tall (Mm) | 310 X 438 X 88 [2U] | 410 X 438 X 88 [2U] | 630 X 438 X 88 [2U] | Lead plane:
530x438x88? [2U]
Batteries is covered:
668x438x88? [2U] | Lead plane:
530x438x88? [2U]
Batteries is covered:
580x438x133? [2U] | Lead plane: 580x438x133 [3U]
Batteries is covered:
580x438x133 [3U] | ||||
Suttle (kilogram) | 12 | 19 | 29.3 | Lead plane: 15
Batteries covers: 48 | Lead plane: 15
Batteries covers: 61 | Lead plane: 18
Batteries covers: 51 | Lead plane: 18
Batteries covers: 61 | ||||
Grow effectMachine | Dimension, deep X wide X is tall (Mm) | 310 X 438 X 88 [2U] | 410 X 438 X 88 [2U] | 500 X 438 X 88 [2U] | 580 X 438 X133 [3U] | ||||||
Suttle (kilogram) | 9 | 12 | 14.2 | 15 | 18 | ||||||
Use environment | |||||||||||
humidity | Relative humidity 20-90 % and spends C (of 0- 40 ° not to written guarantee dew) | Relative humidity 0-95 % and spends C (of 0- 40 ° not to written guarantee dew) | |||||||||
Noise | Little at rice of 50dBA @ 1 | Little at rice of 55dBA @ 1 | Little at rice of 58dBA @ 1 | ||||||||
Control management | |||||||||||
Optional USB of intelligent RS-232 / | Support Windows? 2000/2003/XP/Vista/2008, windows? 7/8, linux, unix, and MAC | ||||||||||
Optional SNMP | Power source management supports SNMP management and network government | ||||||||||